The growing adoption of renewable energy has significantly reduced rotational inertia in modern power grids, increasing their vulnerability to cascading failures. One practical approach is to reinforce inertia by utilizing idle turbines as synchronous condensers. However, inappropriate placement may paradoxically worsen failures due to the Braess paradox.
This study uses the swing equation on a modified UK power grid to identify optimal inertia reinforcement locations. The effectiveness of each site is evaluated through the ratio r(k) of mitigation to adverse effects. Among various topological metrics, the mean shortest path length ℓ shows the highest correlation with r(k) across all reinforcement scales. Nodes with the highest ℓ values are classified as the peripheral group, and they consistently dominate the most effective reinforcement locations across 200 power configurations. These findings demonstrate that reinforcing inertia at topologically peripheral nodes is more effective than targeting well-connected central hubs.